Gas burner Junior Gas

JUNIOR GAS 1 G25
JUNIOR GAS 2 G35, G65, G80
|
|
Junior Gas
|
Power Kw
|
G25
G35
G65
G80
|
12-25
16-34
28-65
50-82
|
|
Enviroment conditions
- supply voltage 230 V (-15 %.... + 10 %) 50 Hz, 1-phase
- power consumption approx. 140 W 0,7 A
- required amount of combustion air for each 10 kWh is 13 m³
- gas pipe connection R ½
- burner protection IP20
- surrounding temperature 0... + 40°C
- main dimensions 362 x 300 x 305 mm
- burner weight approx. 10 kg
|
|
Gases to be used natural gas
for the gases of 2nd family, goups H and E ( equipment categories 12H and 12E )
supply pressure (=inlet pressure) to burner 20 - 200 mbar
gas temperature before gas valve 15... + 40 °C
LPG for the gases of 3rd family, group P ( equipement category 13P )
supply pressure (=inlet pressure) to burner 30 - 200 mbar
gas temperature before gas valve 0... + 40 °C
|
Scope of supply
- single stage gas burner
- the burner can be hinged to both sides
- electrical cord with plug connector
- limit switch
- sight glass
- stepless adujstable air regulation
- connection for measurement of flame signal
- gas valve
- control unit
- flame detector
- signal lamp indicating gas valve operation
- signal lamp indicating burner failure
- self-closing air flap
- gas valve Multiblock wich includes
- gas filter
- gas pressure switch
- pressure regulator
- solenoid valves, 2 pcs
- flange gasket
- mounting screws 2 pcs M10 or 4 pcs M8
- elbows, 2 pcs ( gas pipe )
- gas pipe
- documents
- package
|
Accessories - boiler dual thermostat
- pocket for thermostat
- run hour counter
- flexible gas hose
- piping equipment
Junior Gas brochure >>  |